Victron Phoenix Inverter VE.Direct
VE.Direct communication port
The VE.Direct port can be connected to:
-
A computer (VE.Direct to USB interface cable needed)
-
Apple and Android smartphones, tablets, MacBook’s and other devices (VE.Direct Bluetooth Smart dongle needed)
Fully configurable:
-
Low battery voltage alarm trip and reset levels
-
Low battery voltage cut-off and restart levels
-
Dynamic cut-off: load dependent cut-off level
-
Output voltage 210 - 245V
-
Frequency 50 Hz or 60 Hz
-
ECO mode on/off and ECO mode sense level
Monitoring:
-
In- and output voltage, % load and alarms
Proven reliability
The full bridge plus toroidal transformer topology has proven its reliability over many years.
The inverters are short circuit proof and protected against overheating, whether due to overload or high ambient temperature.
High start-up power
Needed to start loads such as power converters for LED lamps, halogen lamps or electric tools.
ECO mode
WheninECOmode,theinverterwillswitchtostandbywhentheloaddecreasesbelowapresetvalue (min load: 15W). Once in standby the inverter will switch on for a short period (adjustable,default:every2,5seconds).Iftheloadexceedsapresetlevel,theinverterwillremainon.
Remote on/off
A remote on/off switch can be connected to a two-pole connector, or between battery plus and the left-hand contact of the two-pole connector.
LED diagnosis
Please see manual for a description.
To transfer the load to another AC source: the automatic transfer switch
For our low power inverters, we recommend our Filax Automatic Transfer Switch. The Filax features a very short switchover time (less than 20 milliseconds) so that computers and other electronic equipment will continue to operate without disruption.
Available with different output sockets
Schuko UK AU/NZ IEC-320 Nema 5-15R
(male plug included)
DC connection with screw terminals
-
12 Volt
Phoenix Inverter 24 Volt 48 Volt
12/250
24/250
48/250
12/375
24/375
48/375
12/500
24/500
48/500
12/800
24/800
48/800
12/1200
24/1200
48/1200
Cont. power at 25°C (1)
250VA
375VA
500VA
800VA
1200VA
Cont. power at 25°C / 40°C
200 / 175W
300 / 260W
400 / 350W
650 / 560W
1000 / 850W
Peak power
400W
700W
900W
1500W
2200W
Output AC voltage / frequency (adjustable)
230VAC or 120VAC +/- 3% 50Hz or 60Hz +/- 0,1%
Input voltage range
9,2 - 17 / 18,4 - 34,0 / 36,8 - 62,0V
DC low shut down (adjustable)
9,3 / 18,6 / 37,2V
Dynamic (load dependent) DC low shut down
(fully configurable)
Dynamic cut-off, see
https://www.victronenergy.com/live/ve.direct:phoenix-inverters-dynamic-cutoff
DC low restart and alarm (adjustable)
10,9 / 21,8 / 43,6V
Battery charged detect (adjustable)
14,0 / 28,0 / 56,0V
Max. efficiency
87 / 88 / 88%
89 / 89 / 90%
90 / 90 / 91%
90 / 90 / 91%
91 / 91 / 92%
Zero-load power
4,2 / 5,2 / 7,9W
5,6 / 6,1 / 8,5W
6 / 6,5 / 9W
6,5 / 7 / 9,5W
7 / 8 / 10W
Default zero-load power in ECO mode
(default retry interval: 2,5 s, adjustable)
0,8 / 1,3 / 2,5W
0,9 / 1,4 / 2,6W
1 / 1,5 / 3,0W
1 / 1,5 / 3,0W
1 / 1,5 / 3,0W
ECO mode stop and start power setting
Adjustable
Protection (2)
a - f
Operating temperature range
-40 to +65°C (fan assisted cooling) Derate 1,25% per °C above 40°C
Humidity (non-condensing)
max 95%
ENCLOSURE
Material & Colour
Steel chassis and plastic cover (blue Ral 5012)
Battery-connection
Screw terminals
Maximum cable cross-section
10mm² / AWG8
10mm² / AWG8
10mm² / AWG8
25 / 10 / 10mm² /
AWG4 / 8 / 8
35 / 25 / 25mm2 /
AWG2 / 4 / 4
Standard AC outlets
230V: Schuko (CEE 7/4), IEC-320 (male plug included) UK (BS 1363), AU/NZ (AS/NZS 3112)
120V: Nema 5-15R, GFCI
Protection category
IP 21
Weight
2,4kg / 5,3lbs
3,0kg / 6,6lbs
3,9kg / 8.5lbs
5,5kg / 12lbs
7,4kg / 16,3lbs
Dimensions (h x w x d, mm)
(h x w x d, inch)
86 x 165 x 260
3.4 x 6.5 x 10.2
86 x 165 x 260
3.4 x 6.5 x 10.2
86 x 172 x 275
3,4 x 6,8 x 10,8
105 x 216 x 305
4.1 x 8.5 x 12.1
(12V model: 105 x 230 x 325)
117 x 232 x 327
4.6 x 9.1 x 12.9
(12V model: 117 x 232 x 362)
ACCESSORIES
Remote on-off
Yes
Automatic transfer switch
Filax
STANDARDS
Safety
EN-IEC 60335-1 / EN-IEC 62109-1
EMC
EN 55014-1 / EN 55014-2 / IEC 61000-6-1 / IEC 61000-6-2 / IEC 61000-6-3
Automotive Directive
ECE R10-4
-
Nonlinear load, crest factor 3:1
-
Protection key:
-
output short circuit
-
overload
-
battery voltage too high
-
battery voltage too low
-
temperature too high
-
DC ripple too high
-
-